Emi DWPH365 (WHP36-SHC36) Manual de usuario

Busca en linea o descarga Manual de usuario para Acondicionadores Emi DWPH365 (WHP36-SHC36). EMI DWPH365 (WHP36-SHC36) User Manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 3
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
Rome, New York, USAEnviromaster International LLC
JOB NAME: _____________________________________ LOCATION: _______________________________________
PURCHASER: _____________________________________________________________________________________
ENGINEER: _______________________________________________________________________________________
SUBMITTED TO: _________________________________ FOR: REFERENCE [ ] APPROVAL [ ] CONSTRUCTION [ ]
SUBMITTED BY: _________________________________ DATE: ___________________________________________
UNIT DESIGNATION: SCHEDULE #: _______________ MODEL #: ________________________________________
EMI ENGINEERING SUBMITTAL
17
11
1
/
4
57
1
/
2
CAPACITIES:
Cooling 33,000 Btu
Heating – High 31,000 Btu
– Low 18,200 Btu
Indoor Design Temp ºF DB/WB
Cooling 80/67
Heating 70/57
Outdoor Design Temp ºF DB/WB
Cooling 95/75
Heating – High 47/43
– Low 17/15
EER 10.0
SEER 10.0
HSPF 6.8
INDOOR UNIT:
Power Supply 208/230/1/60
Max. Fuse Size 15 Amps (w/o electric heat)
Min. Ampacity .70 Amps (w/o electric heat)
Max. Fuse Size 30 Amps (w/5kw electric heat)
Min. Ampacity 27.9 Amps (w/5kw electric heat)
Sound 54 dBa
Weight 115 Lbs
OUTDOOR UNIT:
Power Supply 208/230/1/60
Max. Fuse Size 30 Amps
Min. Ampacity 19.8 Amps
Sound 67.2 dBa
Weight 155 Lbs
REFRIGERANT PIPING:
Max. Lift 35 Ft
Max. Length 100 Ft
Liquid (OD) 3/8 In
Suction (OD) 7/8 In
STANDARD FEATURES:
• Five-Year Compressor/One-Year Parts Warranty
• I/R Unit Mount Control (w/optional hand-held control)
• Dry Mode for humidity control (when optional electric heat is ordered)
Auto
Restart following a power outage
Anti-Short Cycle protection
• Freeze Protection
• Test Operation
• Side Discharge/Low Profi le Condenser
• Fan Purge
• Manual Reset High Pressure Switch
DWPH365 (WHP36-SHC36)
Rev. 1.1 [12/04]
Vista de pagina 0
1 2 3

Indice de contenidos

Pagina 1 - EMI ENGINEERING SUBMITTAL

Rome, New York, USAEnviromaster International LLCJOB NAME: _____________________________________ LOCATION: _______________________________________PUR

Pagina 2 - Wiring shall

http://[email protected] PART ONE “GENERAL”The Heat Pump air conditioning system shall be an EMI AmericaSeries split system. Th

Pagina 3 - Email: [email protected]

Rome, New York, USAEnviromaster International LLC5780 Success Drive, Rome, NY 13440Phone: 1-800-228-9364FAX: 1-800-232-9364Email: [email protected]